As our world continues to evolve, global manufacturing & research has a need to become increasingly cleaner to meet the high demands of today’s products. Whether it’s pharmaceutical, high-end electronics, semiconductors, aerospace, medical devices, or life sciences, all of these industries require a clean manufacturing environment. These markets are all spaces in which Fisher Scientific has staked a solid foundation designing and building modular cleanrooms. Cleanrooms are controlled environments that are designed to remove pollutants like dust particles, airborne microbes, and aerosol particles. These impurities are filtered out to provide a clean environment for manufacturing or research. Cleanrooms are governed by ISO standards and are classified based on the number of particles per cubic meter of air. High efficiency filters are used to filter out particulate and achieve the desired ISO classification. See the ISO classification chart below.
ISO 14644-1 Cleanroom Standards
Maximum Allowed Particles (per m3)
Air Change Rate (per hour)
Airflow Velocity (ft/min)
Ceiling Cover age
Class
≥0.2 µm ≥0.3 µm ≥0.5 µm ≥1 µm ≥5 µm
ISO 1
2.37
1.02
0.35
0.083
0.0029
360-600
60-100
90-100%
ISO 2
23.7
10.2
3.5
0.83
0.029
360-600
60-100
80-100%
ISO 3
237
102
35
8.3
0.29
360-540
60-90
60-100%
ISO 4
2,370
1,020
352
83
2.9
300-540
50-90
50-90%
ISO 5
23,700
10,200
3,520
832
29
240-480
40-80
35-70%
ISO 6
237,000 102,000 35,200
8,320
293
150-240
25-40
25-40%
ISO 7 2.37×106 1,020,000 352,000 83,200
2,930
60-90
10-15
15-20%
ISO 8 2.37×107 1.02×107 3,520,000 832,000 29,300
5-48
1-8
5-15%
ISO 9 2.37×108 1.02×108 35,200,000 8,320,000 293,000
0-25
0-5
5-10%